2 Installation Guide for Dimming and Switching Panels
Panel Model Number Guide
LCP128TM (LCP) (120 V only)
See page 5 for 230/220-240 V
Modules:
Quantity and Type
Prefix
Example
LCP-2X2D1A4T-1204ML-20
Prefix
LCP = LCP dimming panel
Module Types
_X _S _D _Q _A _M _F _T
List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.
X = Four-Circuit Switching (Relay) (XP)
S = One-Circuit Dimming (1U)
D = Two-Circuit Dimming (2U)
Q = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM
Ballast Control (TVM)
Feed V
oltage
120 for 120 V
Feed
Voltage
Branch Circuit
Breaker Rating
Feed
Type
Feed Type/Input Ratings
FT = Feed-through panel (circuit breakers not included) /
120 V
3ML = 1 phase 3 wire feed (split phase) / 120/240 V
4ML = 3 phase 4 wire feed / 120/208 V
Branch Circuit Breaker Rating
Omit for feed-through panels
20 for 20 A branch circuit breakers
Frequency - All Model Numbers and Voltages
50/60 Hz
Output (Load) Ratings
Module T
ype Rating
XP 16 A per circuit
1U, 2U, 4U 16 A per module
4A 16 A per module, 10 A per output
4M 16 A per module, 5 A per output
(1/4 HP motor),
1 motor per output
4FSQ 2 A per output (single ceiling fan)
TVM 50 mA per channel, 750 mA per system
Module Quantity Limits
Panel Size Feed type TVM 4A 4U 4M
Mini Feed-through NA Any combination up to 3 modules
Mini Feed-through 0-4 Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Mini Breakers NA Any combination up to 3 modules
Mini Breakers 0-4 Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
Standard Feed-through NA Any combination up to 9 modules
Standard Feed-through 0-12 Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Standard Breakers (main lugs) NA Any combination up to 9 modules
Standard Breakers (main lugs) NA Any combination up to 7 modules
Standard Breakers (main lugs) 0-12 Any combination up to 7 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
Standard Breakers (main lugs) 0-12 Any combination up to 5 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Notes
Consult Lutron for panels with custom breaker needs.
TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
TVM = NA is not TVM-ready
XP
0
0
0
0